Engineering
Approved FACPs
DFD APPROVED FIRE ALARM CONTROL/COMMUNICATOR EQUIPMENT
Notes:
Please Note! Fire Alarm Control Panel (FACP) and annunciator locations must be coordinated with the Fire Prevention Bureau (FPB) Systems Inspection and Testing Section prior to installation. This applies to new installations as well as panel replacements. Proposed panels are not permitted to be installed in locations depicted on plans or in existing panel locations until field approval is secured. Please call FPB/Testing at (720) 913-3480 to arrange for field verification of FACP and annunciation panel locations prior to installation.
Panels with Liquid Crystal Display (LCD) are only approved for use with an appropriate Light Emitting Diode (LED) Directory or Graphic Annunciators. Annunciation lights shall be Red for Alarm and Yellow for Trouble and Supervisory Signals [99DBCA Section 907.4.5.2]. Due to product limitations, this may necessitate the installation of multiple annunciation panels.
Class 1 panels are listed for fire alarm use only; combined fire/security/access control systems are not allowed.
All UL- and FM-listed and labeled household fire alarm or combined fire/burglar alarm panels shall be acceptable for installation in individual dwelling units within Denver. Installations must comply with NFPA 72 for Household/Dwelling Unit Systems. If monitored, the monitoring company shall be licensed in Denver. Household systems may supplement code-required single station detectors but shall not replace them.
Fire Alarm Control Panels that require a key or coded password to reset are prohibited. Panel covers that require a key to open are allowed provided a copy of the key is contained in a key box [97UFC Section 902.4].
Panels with 2-level passcode requirements shall not have these codes provided to building personnel.
last updated 5/4/2004 BDE
ADEMCO
678 COMMUNICATOR UL CLASS 1
HA-2000, VIA- 30 CONTROL/COMMUNICATOR (WIRELESS) UL CLASS 2
VISTA-10/SE, Vista20, 20P, VISTA-20SE, SAVS20ADT-1, 20HW, 20AMT, 20AMT3, 20AMTE, 40, 50, 50P, 100, VIA-30P, 4110, 4120, 4140XMPT2, LYNX, SL150, CONTROL/COMMUNICATOR (Wireless) UL CLASS 2
UL File Number “S1632” may be used in lieu of listee name “ADEMCO” on listed household burglar and fire alarm control units
AM100 CONTROL PANEL Consisting of 20AMTE Circuit Board and RES-UL or COM-UL Enclosure UL CLASS 2 (Security Link from AMERITECH)
4153 CONTROL/COMMUNICATOR UL CLASS 2
5110XM CONTROL/COMMUNICATOR UL CLASS 1
VISTA 5130XT ALERT III UL S-1632 UL CLASS 2
VISTA 5140XM CONTROL/COMMUNICATOR UL CLASS 2
5600 ALERT 11 CONTROL PANEL (WIRELESS) 345 MHz UL CLASS 2
5620 CONTROL WITH 5621 WIRED CONSOLE & 5605 (Wireless) CLASS 2
ADPLEX
2000 COMBINATION CONTROL UNIT UL CLASS 2
ADT
CENTRASCAN 3000 CONTROL PANEL UL CLASS 1
ESL 1500, 2000 CONTROL PANEL UL CLASS 1
FOCUS 200 CONTROL/COMMUNICATOR when used with approved, compatible FIRE PANEL IN FIRE ONLY CLASS 1 SYSTEM
FOCUS 45, 48, 75, 100, 200, 300 CONTROL/COMMUNICATOR UL CLASS 2
IRC-3, LSS4 CONTROL PANEL UL CLASS 1
SAFEWATCH CUSTOM, SAFEWATCH PLUS -- same panel as ITI RF COMMANDER 2000 (WIRELESS) CONTROL/COMMUNICATOR UL CLASS 2
UNIMODE 5, 4520 CONTROL/COMMUNICATOR UL CLASS 1
UNIMODE 10 CONTROL/COMMUNICATOR UL CLASS 1
UNIMODE II, 4-16 UL CLASS 1
Unimode 200 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled
UNIMODE 300, 400 CONTROL UL CLASS 1 – cross listed as NOTIFIER AFP-300 AFP-400
UNI*COM COMMUNICATOR for UNIMODE SERIES UL CLASS 1 ADVANTAGE 3400, 3600 CONTROL PANEL UL CLASS 1
UNIMODE 640 - 2-level passcode required for access to initiating and notification circuits
Unimode 9600 - 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled
AES
INTELLINET 7750-F UL CLASS 1, Type-4 two-way RF multiplex system (1996NFPA 72, 4-5-3-4-1) Communicator Only. System shall only be installed where a verifiable “NetCon” value of 5 or less can be maintained. System supervision per NFPA 72 shall be provided. Each installation shall provide a signal routing summary to be maintained on-site.
AIRTECH
MOOSE Z800, Z900, Z1100E, DISCOVERY D1000 CONT/COMM UL CLASS 2
ALARM DEVICE MFG. CO
FA1340C CONTROL/COMMUNICATOR UL CLASS 2
ANSUL
1000, 2000, 3000, 4000 CONTROL/RELEASE UL CLASS 1
ASAP (APEX SECURITY ALARM PRODUCTS), APEX
DESTINY-6100 CONTROL/COMMUNICATOR UL CLASS 2
E SYSTEMS- ADVANTAGE, DEFENDER 11 (WIRELESS) CONTROL/COMMUNICATOR UL CLASS 2
AT&T
8000 SERIES (WIRELESS) 40 MHz CONTROL PANEL UL CLASS 2
8300 CONTROL/COMMUNICATOR UL CLASS 2
8700 COMMUNICATOR used with 8000 CONTROL PANEL UL CLASS 2
AUTOCALL (Thorn)
MDK, MP-AP-400, md/2K CONTROL PANEL UL CLASS 1
XA COMMUNICATOR UL CLASS 1
BHS (BRINKS HOME SECURITY)
1000,2000B, 2000C CONTROL/COMMUNICATOR UL CLASS 2
BMI (BRONCO MFG INC.)
241, 242, 243 CONTROL PANEL UL CLASS 1 BMI (BRONCO MFG INC.) 22032 INTERFACE for RADIO FIRE BOX CLASS 1
CADDX CONTROL INC.
RANGER 8600E, 8980E, 9000E CONT/COMM UL CLASS 2
NetworX NX-8, NX-8E CONTROL/COMMUNICATOR UL CLASS 2
C & K SYSTEMS INC.
2316 CONTROL/COMMUNICATOR (WIRELESS) UL CLASS 2
DETECTION SYSTEMS, INC
DS-7090, 7100 CONTROL/COMMUNICATOR UL CLASS 2
DS7400Xi used as COMMUNICATOR ONLY CLASS 1
DS9471C COMMUNICATOR UL CLASS 1
DICTOGRAPH
G1983, G2200, G4000, G4100DL, G5900, G6200 CONTROL/COMMUNICATOR UL CLASS 1
DBA 1892
(same as Discovery 1000) CONTROL/COMMUNICATOR UL CLASS 2
DSC (DIGITAL SECURITY CONTROLS)
PC1550, 2550, 3000, PC5010 POWER832
WIRELESS USING PC5132-RS, CONTROL/COMMUNICATOR UL CLASS 2
DIGITIZE
SYSTEM 3000 COMMAND AND CONTROL CENTER UL CLASS 1
DIGITAL MONITORING PRODUCTS, INC
XR5FC, XR5SL CONTROL/COMMUNICATOR UL CLASS 1, XR10, XR20 CONTROL/COMMUNICATOR UL CLASS 2, INC XR200 when configured for UL864 with 1-893 dual phone module, 1-350-81 RED PANEL. NO security functions, no wireless options, UL CLASS 1
DISCOVERY
1000, 5000 CONTROL/COMMUNICATOR UL CLASS 2
EAGLE (EGL)
8000-8000DL CONTROL/COMMUNICATOR UL CLASS 2
ESL (ELECTRO SIGNAL LAB)
1500
2500 CONTROL/COMMUNICATOR UL CLASS 1 (only when equipped with yellow system trouble LED)
EST (EDWARDS SYSTEMS TECHNOLOGY)
5721B, 5754B-2Z, 5800 CONTROL PANEL UL CLASS 1
MODEL FCC, EST-1Z1/2Z1,
Quickstart QSC, QS1 and QS4 Enable/Disable barrel key shall be removed; level-two password shall be provided (access at this level shall not be provided to builidng personnel); panel shall be provided with a locking door (key in secure key box)
EST-2, LSS1, ESA2000, IRC-3, 6616, 6632, EST-3, CONTROL UL CLASS 1
FARADAY
15108A, 15112A, 15116A, 15220, 15240
MPC-1000, MPC-1000plus level 2 password protection shall be provided (access at this level shall not be provided to building personnel); serial annunciator is required; auto-silence feature for NAC shall be set to "None" and locked in position; "Inhibit" function not allowed; operation as a "Tornado Warning" not allowed
MPC 2000, LIFEWATCH 400, 500 CONTROL UL CLASS 1
FAST (FIRE ALARM SYSTEMS TECH)
CM1N, RMDP-1N CONTROL MODULES UL CLASS 1FBII (FIRE BURGLARY INSTRUMENTS, INC.) XL-1, XL-2, XL-2P, XL-2T, XL-4C, XL-31, STAR XL4600, XL4600/DL, XL4605/B, XL4800/EX, XL4805/EZ, LEGEND 70/80/100 UL CLASS 2
FCI (FIRE CONTROL INSTRUMENTS)
FC-10C UL CLASS 1 CONTROL/COMMUNICATOR
7100 SERIES including Netsolo Broadband (panel enable/disable keyswitch shall be removed), 7200 SERIES, FAC3 COMMAND, FC72, FCID SERIES, SBP-2, SBP-4 CONTROL UL CLASS 1
FEDERAL SIGNAL CORP. ( Autocall ) FireLarm Systems
2000, 3000, 4000, 6000, 8000 CONTROL PANEL UL CLASS 1
FENWAL
2210, 2212, 2410, 2412, 3210 CONTROL PANEL UL CLASS 1
FENWALNET
1000 CONTROL PANEL UL CLASS 1
2000 CONTROL PANEL RELEASING DEVICE UL CLASS 1
FIKE
CHEETAH CONTROL PANEL UL CLASS 1
INTELLA-SCAN II, RHINO CONTROL UL CLASS 1
SHP CONTROL/RELEASE UL CLASS 1
10-038, 039 CONTROL/RELEASE UL CLASS 1
FIRECOM
LS1000 (same panel as SECUTRON MR-2400) CONTROL UL CLASS 1
FIRE LITE INC. [see Denver Field Bulletin]
MINISCAN 112/124, 424A, 4012, 4024 CONTROL PANEL UL CLASS 1
SENSISCAN 1000, 2000 CONTROL PANEL UL CLASS 1
MS-4412B, MS-4424 WHERE ONLY 1 SUPERVISORY CIRCUIT REQUIRED,
MS-4424B, MS-4812/MS-4824,MS-5012, MS-5024, MS-5024UD, MS-5210UD CONTROL/COMMUNICATOR UL CLASS 1
UDACT-F, Noti*Fire 911A COMMUNICATOR UL CLASS 1
2000, MP-12/24 CONTROL PANEL UL CLASS 1
MS-9200, MS-9200UD, MS9600 - 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled. Panels with Liquid Crystal Display (LCD) are only approved for use with an appropriate Light Emitting Diode (LED) Directory or Graphic Annunciators. Annunciation lights shall be Red for Alarm and Yellow for Trouble and Supervisory Signals [99DBCA Section 907.4.5.2]. Due to product limitations, this may necessitate the installation of multiple annunciation panels.
MRP 4424 RELEASE/CONTROL PANEL UL CLASS 1
FIRETEK
SYSTEM 210 CONTROL PANEL UL CLASS 1
FIRST ALERT
FA120C, FA145C, FA150C, FA160C CONTROL PANEL (WIRELESS) UL CLASS 2 (FOR FA1340C,SEE ALARMDEVICE MFG. CO.)
GAMEWELL
FLEXALARM 300\3000, 500 CONTROL PANEL UL CLASS 1
FLEXALERT, FLEX 401-02 CONTROL PANEL UL CLASS 1
IDENTIFIRE NETWORK SYSTEM 2 CONTROL PANEL UL CLASS 1
IDENTIFLEX 610, 630, 650 CONTROL PANEL UL CLASS 1
FS 140, ZANS 400 CONTROL PANEL UL CLASS 1
GENERAL SIGNAL (MIRTONE)
7516, 7532 CONTROL PANEL UL CLASS 1
GENESYS
824 CONTROL/COMMUNICATOR UL CLASS 2
GRINNELL
TFX-500M, TFX-800M CONTROL PANEL UL CLASS 1
HARRINGTON SIGNAL CO.
HS-2200/2400, HS-3000, HS-3030, HS-3400 CONTROL PANEL UL CLASS 1
HOME AUTOMATION, INC. (HAI)
OMNI CONTROL/COMMUNICATOR UL CLASS 2, 1503 VERSION 2 VOICE MESSAGE
& 1503-LC, OMNILT(21A00-1) MODEL CONTROL/COMMUNICATOR UL CLASS 2
HONEYWELL [see Denver Field Bulletin]
5600, 5800, D5924 CONTROL/COMMUNICATOR UL CLASS 1
DeltaNet FS90 CONTROL PANEL UL CLASS 1
XLS-1024UD, XLS-9200UD, XLS-9600 - 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled
ESTATE 200 CONTROL PANEL UL CLASS 2
SYSTEM 1500, 2000, 6000, 7000 (WIRELESS) CONTROL/COMM. PANEL UL CLASS 2
XLS200, XLS1000 without "Optional Display Module Panel"
INTELLIGUARD 5503, 5505, 5700 CONTROL/COMMUNICATOR UL CLASS 2
TOTALHOME CONTROL PANEL UL CLASS 2
XLS-2Z3-R CONTROL PANEL UL CLASS 2
INOVONICS VISION PLUS
C-2020 CONTROL/COMMUNICATOR (WIRELESS) UL CLASS 2
ITI (Interactive Technologies, Inc.)
SX-V, RF COMMANDER 2000, (SECURITY PRO 3000),
CARETAKER+(SECURITY PRO 4000), ULTRAGARD 60-620, ULTRAGUARD 60-626, (SECURITY PRO 5000)
CONTROL/COMMUNICATOR (WIRELESS) UL CLASS 2
4720 when configured for 1 button reset and 1 button silence, (same as SILENT KNIGHT 4720) CONTROL/COMMUNICATIOR UL CLASS 1
JOHNSON CONTROLs
IFC-1010, 2020 CONTROL PANEL UL CLASS 1
KIDDE
200, KDR-1000 CONTROL PANEL UL CLASS 1
LANDIS & STAEFFA INC
ALS3 CONTROL PANEL UL CLASS 1
LINEAR
DF-16, 21st SENTRY CP-90 (WIRELESS) CONTROL/COMMUNICATOR UL CLASS 2
DVS-1200, DVS-2400 (WIRELESS) CONTROL/COMMUNICATOR CLASS 2 ONLY
MERLIN (AUTOCALL)
CONTROL PANEL UL CLASS 1
MIRCOM
FX-2000H, FA-1000 to be used with CONTROL PANELS COMMUNICATOR ONLY,
FX-2000 No Conventional Devices Allowed on Addressable Loops -- 2 Wire Smoke Detectors must be listed
& compatible with this Panel - to be used with Control Panels Communicator only
FX-2000 series includes FX-2017 audio evacuation system; approved annunciator required; auto-configure function shall be password protected, configurable input switches shall not be programmed for initiating or notification device or zone disable or City disconnect; 2-level hierarchy shall be provided for passcodes; passcodes at this level shall not be provided to buildling personnel; no conventional devices are allowed on addressable loops; for use with UDACT-100A Digital Communicator
MIRTONE
MIR2 w/two-level passcode protection and LED annunciator
MOOSE
Z800, Z900, Z1100E CONTROL/COMMUNICATOR UL CLASS 2
MORSE
MDC-16 CONTROL/COMMUNICATOR WITH MDC-FSM MODULE UL CLASS 1
NAPCO
MAGNUM ALERT 800, 825, 850/850M, 900, 1000, 1008, 2000, 3000, 2600 SERIES, 6024 CONTROL/COMMUNICATOR UL CLASS 2
MAGNUM ALERT 1000e, 1008e/1008eM, 1016e/1016eM, CONTROL/COMMUNICATOR UL CLASS 2
SIGNATURE SS4501, SS4504, SS4509, SS4516, SS4516M, 5500 CONTROL/COMMUNICATOR UL CLASS 2
Notifier
AFP-100 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled
500, AFP-200, AFP-400, AFP1010, AM2020, 5000, SFP-400, SGL-CSGL-404, ONYX-640 CONTROL UL CLASS 1
RP-1001 DELUGE CONTROL PANEL UL CLASS 1
911A, SFP-1024, 1024E CONTROL/COMMUNICATOR UL CLASS 1
NFS-3030 2-level passcode required for access to initiating and notification circuits
OPTEX MORSE INC.
GENESYS 824 CONTROL/COMMUNICATOR UL CLASS 2
PFS (PROFESSIONAL FIRE SYSTEMS)
4A, 8A, 12A CONTROL UL CLASS 1
POTTER
PDC-3 COMMUNICATOR UL CLASS 1
PFC-4410 RELEASING PANEL UL CLASS 1, PROTECTOWIRE ACR-1600LTI CONTROL PANEL FM CLASS 1
PFC-9000 & 9100 with auto-configure function password protected; configurable input switches shall not be programmed for initiating or notification device, zone disable or city disconnect; two-level hierarchy shall be provided for passcodes;passcodes at this level shall not be provided to building personnel
PROTECTOWIRE
FS-2000 SERIES DELUGE CONTROL PANEL FM CLASS 1
Pyro-Chem
PCR-100 (panel approved for releasing service with Department-approved graphic annunciator)
PYROTRONICS
SYSTEM 3 CP-35, XL-3, IXL, MXL, MXL-IQ, SXL, CONTROL
INS-2 (IDENTIFIRE NETWORK SYSTEM 2)
RADIONICS
D2071, D2071A, D6112, D7112 COMMUNICATOR
OMEGA 8112F, CONTROL/COMMUNICATOR
D9412G**, D7412G**, D9124** CONTROL/COMMUNICATOR UL CLASS 1
**Note: D9412G, D7412G and D9124 units require separate annunciator and additional components as follows: Remote keypad D1256 is required w/only; “Trouble Silence”, “Alarm Silence” and “System Reset” functions. “System Reset” shall reset the control panel, LED annunciator and keypad display simultaneously. Keypad shall be located under an approved transparent cover secured with a knox lock. Contact 720.913.3480 for details. [see "Technogram" 9/15/2002]
D9124
SAFETECH
2000 SERIES AND 3000 SERIES CONTROL PANELS
SECUTRON INC.
MR-2400, MR-2600, MR-2605, MR-2608, MR-2616, MR-2900 CONTROL UL CLASS 1
SIEMENS
PXL CONTROL PANEL UL CLASS 1
SIEMANS BUILDING TECHNOLOGIES INC
MXL, MXL-IQ, SXL CONTROL
FireFinder XLS w/SSD-C system display w/control keyswitch removed. System display to be located behind a secured, see-through door. 2-level passcode protection to be provided for zone & device disable functions. A sign shall be provided mounted inside the door stating: “All events must be acknowledged and notification circuits silenced prior to Reset.”
FireSeeker Model FS-250 w/passcode protection for access to maintenance functions and approved LED annunciator; “Auto-silence” feature shall not be used
SILENT KNIGHT
2820 (with options) 4720, 5104B, 5107, 5204 (without optional remote keypad), C-6000 (RELEASE) CONTROL/COMMUNICATOR
SK-4224 CONTROL PANEL in approved applications
IntelliKnight 5700 and IFP-50 with 2-level passcode protection and approved directory or graghic annunciator
IFP-100 CONTROL/COMMUNICATOR: requires modified door with transparent view panel to prevent unauthorized access to “Silence” and “Reset” buttons. “Silence” and “Reset” functions shall not require a code to operate.
IFP-100VIP, IFP-1000VIP Control Panels with voice evacuation. In highrise applications, separate VIP-50 transponders are required for "A" and "B" risers. "Silence" and "Reset" features shall not require a code to operate. 2-level passcode protection is required to access device, zone and output disable functions
SIMPLEX
2120 MULTIPLEX, 4001, 4002, 4004, 4005, 4010, 4020, 4100, 4120 CONTROL, 2080-9023,
2080-9024 COMMUNICATOR
4100U, 4100+ (UL UOJZ.S771); panels shall be provided with see-thru, lockable doors limiting access to authorized personnel -- keys in Knox Box
SONITROL [see Denver Field Bulletin]
ADVANTAGE ULF 3012, 3024, 3350, 3450, 3650 CONTROL/COMMUNICATOR UL CLASS 1
10, 198, 636 - 2-level passcode required for access to initiating and notification circuits. Silence inhibit and Auto-Silence timer functions shall be disabled
SPECTRONICS CORP.
324MX, 640, 641 CONTROL/AUDIO PANEL UL CLASS 1
THORN (Autocall)
MDK, MP-AP-400, md/2K, TFX-500M/800M CONTROL UL CLASS 1
XA COMMUNICATOR UL CLASS 1
THORN (Firequest)
200, KDR-1000 CONTROL PANEL UL CLASS 1
UNITY SYSTEMS INC.
MCPU2 CONTROL PANEL UL CLASS 2
VECTOR
3000 CONTROL/COMMUNICATOR UL CLASS 2
WELLS FARGO
SMT-1/SMT-4 MULTIPLEX TRANSPONDER UL CLASS 2
WESTINGHOUSE
RF COMMANDER, HA-2000A (WIRELESS) CONTROL/COMMUNICATOR UL CLASS 2